the information found in our forums, are from many sources, qualified and un qualified as is the nature of the internet, and as such you use this information at your own risk. No liability directly or indirectly will be accepted by aussiedistillers.com.au, administration, the mod team or their heirs, whatsoever.
Regards,
aussiedistiller team.
by Triangle » Sat May 27, 2017 1:48 pm
I think he means fuse in the power controller?
-
Triangle
-
- Posts: 149
- Joined: Fri Nov 07, 2014 10:03 pm
- Location: Adelaide
- equipment: To be anounced!
by Lowie » Sat May 27, 2017 2:17 pm
Righto fellas, I'll take that under advice. Off to jay car tomorrow. :handgestures-thumbupleft:
-
Lowie
-
- Posts: 712
- Joined: Sun May 24, 2015 1:32 pm
- Location: Crow eater
- equipment: 4", 4 plate "Frankenfurter" copper bubbler and blockhead on a 50L 3000W electric boiler, 10000W controller - don't even know why I need that much, all grain HERMS system through 18G HLT keg and 50L mash tun.
by Clubby » Sun Jun 04, 2017 5:54 pm
Finally got to use the power controller on the weekend. 3 runs and no problems with it at all. :teasing-nutkick:
-
Clubby
-
- Posts: 54
- Joined: Sat Sep 03, 2016 5:51 pm
- Location: Gold Coast Hinterland
- equipment: FSD 50L milk can boiler, Neutralizer 5 plate, blockhead tee and a Gin Caddy. 2 x 2400 elements.
Turbo 500, an old 2" pot, too suit a T500 boiler collecting dust
by CyBaThUg » Sun Jun 04, 2017 6:18 pm
I got one of these threw it in a j box wired it up and got the sparkies to check it done maybe 20 or so runs with it
You do not have the required permissions to view the files attached to this post.
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by Lowie » Mon Jun 05, 2017 8:22 am
I rewirded my fuse back in as suggested. Blew two fuses before taking it back out again on the weekend (had a run to do). Guess I best find a new electronics person to check it out. :handgestures-thumbdown:
-
Lowie
-
- Posts: 712
- Joined: Sun May 24, 2015 1:32 pm
- Location: Crow eater
- equipment: 4", 4 plate "Frankenfurter" copper bubbler and blockhead on a 50L 3000W electric boiler, 10000W controller - don't even know why I need that much, all grain HERMS system through 18G HLT keg and 50L mash tun.
by Plumby » Mon Jun 05, 2017 9:09 am
CyBaThUg wrote:I got one of these threw it in a j box wired it up and got the sparkies to check it done maybe 20 or so runs with it
:text-+1: I got a safety switch wired into mine as well. I got mine for $13 including delivery at the time.
-
Plumby
-
- Posts: 1175
- Joined: Sat Aug 02, 2014 7:19 am
- Location: South East Queensland
- equipment: 50 litre keg boiler with a 2200watt element and a 2 inch pot still called Shaniqua with a 32mm over 19mm 800mm long liebig condenser attached.
by CyBaThUg » Mon Jun 05, 2017 11:13 am
Yeah so did I just took a screenshot of the first one I saw
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by CyBaThUg » Mon Jun 05, 2017 11:14 am
Mine is on a dedicated 15 amp circuit
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by scythe » Wed Jun 07, 2017 6:21 am
Lowie:
Sounds like you have too much load on your distilling circuit.
Have you thought about getting some of those resettable fuses rather than running old school wire?
Or better yet disconnect all the other appliances on the circuit while you are doing a run.
When they wired my house they put ALL power points on one circuit and lights on another.
Yes i have a smallish house but its a bit annoying that i can't make a cup of tea or do thw ironing while the dryer is on.
-
scythe
-
- Posts: 1860
- Joined: Thu Nov 14, 2013 6:34 am
- Location: Central West NSW
- equipment: Dreaming of a 4" bubbler
by Lowie » Wed Jun 07, 2017 8:57 am
scythe wrote:Lowie:
Sounds like you have too much load on your distilling circuit.
Have you thought about getting some of those resettable fuses rather than running old school wire?
Or better yet disconnect all the other appliances on the circuit while you are doing a run.
When they wired my house they put ALL power points on one circuit and lights on another.
Yes i have a smallish house but its a bit annoying that i can't make a cup of tea or do thw ironing while the dryer is on.
I thought about that mate when I first started using the controller. I have a dedicated 10A circuit running to the shed from the meter box. Everything, including lights run off this circuit, so before I start the run I switch everything off in the shed so theoretically I have 2400w to play with. The element in the boiler is 3000w so I have the controller turned down to 16 (maximum power is 20 on the dial) which I'm just taking a wild guess is somewhere near or under 2400w. It must be something to do with the power to the controller as if I go over 2400w the shed circuit breaker throws. I'm putting it down to dodger Chinese equipment...
:think:
-
Lowie
-
- Posts: 712
- Joined: Sun May 24, 2015 1:32 pm
- Location: Crow eater
- equipment: 4", 4 plate "Frankenfurter" copper bubbler and blockhead on a 50L 3000W electric boiler, 10000W controller - don't even know why I need that much, all grain HERMS system through 18G HLT keg and 50L mash tun.
by CyBaThUg » Wed Jun 07, 2017 12:24 pm
Maybe your controller can't handle more than 2400 watt what is it rated for
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by CyBaThUg » Wed Jun 07, 2017 12:25 pm
I thought anything over 2400 should be on a 15 amp circuit well I think
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by CyBaThUg » Wed Jun 07, 2017 12:33 pm
I'm no sparky but I think if using a 240v circuit divide by 3000 watt gives u 12.5amps so possibly to much for a ten amp plug hopefully someone else can help u sorry it's all I can come up with
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by Minpac » Wed Jun 07, 2017 12:39 pm
10A x 240V = 2400W max. There's probably some efficiency losses in the power controller, and maybe some losses in cable length, so the real life max might be somewhere lower than 2400w.
-
Minpac
-
- Posts: 310
- Images: 0
- Joined: Sun Oct 25, 2015 5:41 pm
- Location: SE QLD
- equipment: 2" pot, 2" VM
by Lowie » Wed Jun 07, 2017 12:46 pm
CyBaThUg wrote:Maybe your controller can't handle more than 2400 watt what is it rated for
It's rated at 6000w...
-
Lowie
-
- Posts: 712
- Joined: Sun May 24, 2015 1:32 pm
- Location: Crow eater
- equipment: 4", 4 plate "Frankenfurter" copper bubbler and blockhead on a 50L 3000W electric boiler, 10000W controller - don't even know why I need that much, all grain HERMS system through 18G HLT keg and 50L mash tun.
by Lowie » Wed Jun 07, 2017 12:49 pm
CyBaThUg wrote:I thought anything over 2400 should be on a 15 amp circuit well I think
You're absolutely right there mate. But, by turning the potentiometer down I'm figuring that I'm turning the wattage of the heater down. Then again, maybe I'm turning down the input voltage? I really wish that I had accepted the sparky apprenticeship instead of the fitter...
-
Lowie
-
- Posts: 712
- Joined: Sun May 24, 2015 1:32 pm
- Location: Crow eater
- equipment: 4", 4 plate "Frankenfurter" copper bubbler and blockhead on a 50L 3000W electric boiler, 10000W controller - don't even know why I need that much, all grain HERMS system through 18G HLT keg and 50L mash tun.
by CyBaThUg » Wed Jun 07, 2017 1:02 pm
Haha I'm doing a fitters apprenticeship now after a boily apprenticeship over being an apprentice lol
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by CyBaThUg » Wed Jun 07, 2017 1:05 pm
Yeah so if your element is 3000 watt when u turn it up u probably r going over the 2400 allowed and the reason for the breaker flicking off
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by CyBaThUg » Wed Jun 07, 2017 1:06 pm
Ok sorry didn't read properly
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still
by CyBaThUg » Wed Jun 07, 2017 1:09 pm
Maybe test the controller on something smaller like a fan and c if it works
-
CyBaThUg
-
- Posts: 493
- Joined: Thu Sep 27, 2012 7:54 pm
- Location: townsville
- equipment: pot still